Research · Selected work

Risk-Based Ventilation for Indoor Sports

A Wells–Riley analysis comparing outdoor-air ventilation and portable-air-cleaner capacity for infection-risk control in a sports-center scenario.

Period
2021
Status
Course research
Perspectives
Research · Engineering

30-second case brief

Question, responsibility, method, result.

Question
A Wells–Riley analysis comparing outdoor-air ventilation and portable-air-cleaner capacity for infection-risk control in a sports-center scenario.
Responsibility
Collaborative analysis and reporting
Methods
Course research · 2021 · J. Moussa and R. Tajik
Result
Course research

Project scope and responsibility

Role
Collaborative analysis and reporting
Context
Course research · 2021 · J. Moussa and R. Tajik
Focus
Ventilation · Infection risk · Wells–Riley · Clean air delivery · Indoor sports
01 / 01

Overview

This project used a Wells–Riley model to compare outdoor-air ventilation and portable-air-cleaner capacity for a gym or sports-center zone. For a 150 m³, 50 m² case with one-hour occupancy, the analysis tested combinations intended to keep the event reproduction number below 0.5. It showed that conventional per-person ventilation ranges may be insufficient in high-activity scenarios and that higher clean-air-delivery rates can offset some outdoor-air demand. In the most demanding activity category studied, the model indicated up to a 25 percent reduction in required outdoor air. These results are scenario-based, not universal design values.

Contact

Interested in hiring me?