Research · Selected work
Risk-Based Ventilation for Indoor Sports
A Wells–Riley analysis comparing outdoor-air ventilation and portable-air-cleaner capacity for infection-risk control in a sports-center scenario.
- Period
- 2021
- Status
- Course research
- Perspectives
- Research · Engineering
30-second case brief
Question, responsibility, method, result.
- Question
- A Wells–Riley analysis comparing outdoor-air ventilation and portable-air-cleaner capacity for infection-risk control in a sports-center scenario.
- Responsibility
- Collaborative analysis and reporting
- Methods
- Course research · 2021 · J. Moussa and R. Tajik
- Result
- Course research
Project scope and responsibility
- Role
- Collaborative analysis and reporting
- Context
- Course research · 2021 · J. Moussa and R. Tajik
- Focus
- Ventilation · Infection risk · Wells–Riley · Clean air delivery · Indoor sports
Overview
This project used a Wells–Riley model to compare outdoor-air ventilation and portable-air-cleaner capacity for a gym or sports-center zone. For a 150 m³, 50 m² case with one-hour occupancy, the analysis tested combinations intended to keep the event reproduction number below 0.5. It showed that conventional per-person ventilation ranges may be insufficient in high-activity scenarios and that higher clean-air-delivery rates can offset some outdoor-air demand. In the most demanding activity category studied, the model indicated up to a 25 percent reduction in required outdoor air. These results are scenario-based, not universal design values.