Data hall thermal explorer

Interactive tool · calculated thermal scenarios

Operate the data hall.

Change the load, supply temperature, airflow, and containment. Compare rack-zone inlet temperatures, cooling margin, and a four-minute unit outage.

24 racks · four analytical zones3 units active
Hot return aisle ↑
R1R2R3R4R5R6R7R8R9R10R11R12
→ Cold supply aisle ←
R13R14R15R16R17R18R19R20R21R22R23R24
Hot return aisle ↓
Zone 120.4°C
Zone 220.4°C
Zone 320.4°C
Zone 420.4°C
IT heat load163.2 kW
Cooling capacity margin62.4 kW
Modeled cooling + fans54.7 kW

Hottest inlet · 15-minute event

05915 min35°C16°C27°C reference

How the calculation works +

Four rack zones use sensible heat balance and an assumed recirculation fraction. The mixing rise is r/(1-r) × rack temperature rise. Capacity and COP follow explicitly assumed outdoor-temperature curves. The transient combines a 40-second mixing response with a 6 MJ/K effective hall heat capacity. Zone colors show calculated zone averages.

The temperature comparison uses the ASHRAE A1-A4 recommended dry-bulb inlet range of 18-27°C.

Equations, inputs, scenario table, and references ↗